Diseño de una planta de tratamiento de aguas residuales para la Universidad Politecnica Salesiana, Sede Quito, Campus Sur
The general objective of the study was to design a treatment plant for the Universidad Politécnica Salesiana Sede Quito Campus Sur (UPS-Q-S), which was the measurement of the flow from the University with a lignigrafo-sampler giving a total of 0,944 l/s. The sample that was taken from the campus...
Autor Principal: | Rogel Cando, Karla María |
---|---|
Otros Autores: | Gallardo Morales, Marcos Alejandro |
Formato: | bachelorThesis |
Idioma: | spa |
Publicado: |
2015
|
Materias: | |
Acceso en línea: |
http://dspace.ups.edu.ec/handle/123456789/7555 |
Etiquetas: |
Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
|
Sumario: |
The general objective of the study was to design a treatment plant for the
Universidad Politécnica Salesiana Sede Quito Campus Sur (UPS-Q-S), which was
the measurement of the flow from the University with a lignigrafo-sampler giving a
total of 0,944 l/s. The sample that was taken from the campus was sent to the
CICAM (Centre for research and environmental Control) for their respective analysis
and characterization.
They were developed and presented three different and autonomous processes such
as wastewater treatment, to consider different options according to different
characteristics such as advantages and disadvantages.
Taking into consideration the flow proceeded to a first design which consisted of a
facultative lagoons and aeration system.
As second design was a reactor blanket of ascending flow (UASB), which takes
place in a tank in an anaerobic atmosphere and process that requires that the water
income has certain characteristics as a pH slightly acid and low presence of solid
materials.
As the third design arose as a septic tank, common treatment used for most domestic
water treatment. It took into account environmental and topographical characteristics
of the land, the costs of construction and operation. .
This study concludes that the most effective solution for treating waste effluents
from the UPS-Q-S is the UASB that involves a treatment of low-cost maintenance
and high removal of contaminants discharges in liquid |
---|